Re: APC Matrix 5000 question(s)

From: Matthew Sullivan (no email)
Date: Wed Aug 02 2006 - 00:54:42 EDT

  • Next message: Peter Dambier: "Re: mitigating botnet C&Cs has become useless"

     wrote:
    > Update: I replaced the batteries today, and indeed, several of the old
    > ones (mostly in the first pack) were split and some had popped a couple of
    > their "sealed" tops.
    >
    > I left for several hours and came back to the house stinking like burning
    > rubber. The new batteries are apparently melting the terminal rubber
    > insulation. I had to throw it back into bypass mode and unplug that pack
    > (the only one with new batteries!)
    >
    > Any ideas to the cause? The status screens looked ok. ("no bad batteries"
    > again)
    >
    Tip: Except where a newly supplied battery is faulty, replace all or
    none - across all your packs connected to the same UPS.

    / Mat