    I've had this APC Matrix 5000 with 3 XR battery packs for almost 6 years
    now, and it's generally been rock solid, with lots of uptime when
    needed...the average laod is only around 24%, which probably helps.

    At around 1am last night, my network had a power event which brought
    everything down...everything came back up on its own except a customer's
    colo server, which has a dead power supply and one of my servers, which
    had a dead drive in its RAID 1 (the other was ok).

    I looked at the UPS menus...status, etc and everything looked 100%, with
    "BAD BATTS 0", 12 hours+ of est runtime, etc. I then decided to run a
    battery test, which I stupidly did without going into bypass mode first
    (kinda thought it would do that automatically), power was interrupted and
    the alarm started beeping with a "BAD BATT" light, after which power came
    back on and it eventually quieted down and looks the same as it did
    before...still "zero bad batteries" in the status menu, 100% etc.

    Any clues what the problem is here? Is it the UPS itself, or one of the
    battery packs? If the latter, is there a way to find out which one?

    TIA!